Stick GAMMAPAC

Gammapac panels are multipurpose panels designed to meet a wide range of applications.

They are suitable for all the coverings used with access flooring.


Le contenu de cette page nécessite une version plus récente d?Adobe Flash Player.

Obtenir le lecteur Adobe Flash

Access floor panel

Bullet3 Composition :
The Gammapac panel is made up as follows :
- A high density resin bonded core, thickness 30 mm or 38 mm.
- A bottom plate of galvanized steel.
- An ABS surround, heat bonded to the edge of the core.

Bullet3 Coverings :
The Gammapac panel is available with the following coverings :
- High pressure laminate.
- Vinyl.
- Linoleum.
- Textile.
- Rubber.

Bullet3 Dimensions :
- Standard size : 600 mm
- Size 675 mm for thickness 38 mm.
- Special sizes, on request.

Bullet3 Options :
For panels without covering only :
- Top varnished.
- Top plate galvanized steel.

Bullet3 Fire classification:
The Gammapac panel is classed M1 ( SNPE report nr 15706-12). The Gammapac panel, 38mm thick, is classed F 30, according to DIN 4102.

Bullet3 Electrical resistance :
It varies from 5x108 to 2x1012 Ohms, depending on the properties of the covering.

Bullet3 Acoustic :
The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 44 to 50 dBA, depending on the thickness of the panel and the covering (Dn,f,w according to Standard NF EN ISO 10848-2).

Bullet3 PDF Download :

France

Bullet3 Print this page : print

Load Classes
  Framework Class Certificate
Gammapac 30
self-supporting
1A ( or 1B or 2C )
nr 03.10.30.08
Gammapac 30 with HPL
self-supporting
2A ( or 2B or 3C )
nr 03.10.30.11
Gammapac 30 with HPL
stringers 30/15
2A ( or 3B or 4C )
nr 03.10.30.02
Gammapac 38
self-supporting
2A ( or 4B or 5C )
nr 03.07.10.06
Gammapac 38
stringers 30/15
4A ( or 5B or 5C )
nr 03.07.10.08
Gammapac 38
stringers 45/15
5A ( or 5B or 5C )
nr 03.07.10.10

Survey Institute : SOCOTEC CONSULTING.
All technical changes reserved without further notice.

NB :A system classed 2A is a system for which the ultimate load is at least 6 kN ( load class 2 ).
The working load of this system is at least 3kN, with a safety factor of 2, for a deflection less than 2.5mm ( deflection class A).
See tables below for the other classes.
   

Load classes according to NF EN 12825
and using safety factor = 2.0

LOAD CLASS 1 2 3 4 5 6
Ultimate load > 4 kN > 6 kN > 8 kN > 9 kN > 10 kN > 12 kN
Working load > 2 kN > 3 kN > 4 kN > 4.5 kN > 5 kN > 6 kN
Deflection class Maximum deflection
A ( the most stringent )
2.5 mm
B 3.0 mm
C ( the least stringent )
4.0 mm