Stick GAMMAPAC

Gammapac panels are multipurpose panels designed to meet a wide range of applications.

They are suitable for all the coverings used with access flooring.


Access floor panel

Bullet3 Composition :
The Gammapac panel is made up as follows :
- A high density resin bonded core, thickness 30 mm or 38 mm.
- A bottom plate of galvanized steel.
- An ABS surround, heat bonded to the edge of the core.

Bullet3 Coverings :
The Gammapac panel is available with the following coverings :
- High pressure laminate.
- Vinyl.
- Linoleum.
- Textile.
- Rubber.

Bullet3 Dimensions :
- Standard size : 600 mm
- Size 675 mm for thickness 38 mm.
- Special sizes, on request.

Bullet3 Options :
For panels without covering only :
- Top varnished.
- Top plate galvanized steel.

Bullet3 Fire classification:
The Gammapac panel is classed M1 ( SNPE report nr 15706-12). The Gammapac panel, 38mm thick, is classed F 30, according to DIN 4102.

Bullet3 Electrical resistance :
It varies from 5x108 to 2x1012 Ohms, depending on the properties of the covering.

Bullet3 Acoustic :
The acoustic insulation measured between 2 adjacent rooms, separated by a densely insulated partition, varies from 44 to 50 dBA, depending on the thickness of the panel and the covering (Dn,f,w according to Standard NF EN ISO 10848-2).

Bullet3 PDF Download :

France

Bullet3 Print this page : print

Load Classes
  Framework Class Certificate
Gammapac 30
self-supporting
1A ( or 1B or 2C )
nr 03.10.30.08
Gammapac 30 with HPL
self-supporting
2A ( or 2B or 3C )
nr 03.10.30.11
Gammapac 30 with HPL
stringers 30/15
2A ( or 3B or 4C )
nr 03.10.30.02
Gammapac 38
self-supporting
2A ( or 4B or 5C )
nr 03.07.10.06
Gammapac 38
stringers 30/15
4A ( or 5B or 5C )
nr 03.07.10.08
Gammapac 38
stringers 45/15
5A ( or 5B or 5C )
nr 03.07.10.10

Survey Institute : SOCOTEC CONSULTING.
All technical changes reserved without further notice.

NB :A system classed 2A is a system for which the ultimate load is at least 6 kN ( load class 2 ).
The working load of this system is at least 3kN, with a safety factor of 2, for a deflection less than 2.5mm ( deflection class A).
See tables below for the other classes.
   

Load classes according to NF EN 12825
and using safety factor = 2.0

LOAD CLASS 1 2 3 4 5 6
Ultimate load > 4 kN > 6 kN > 8 kN > 9 kN > 10 kN > 12 kN
Working load > 2 kN > 3 kN > 4 kN > 4.5 kN > 5 kN > 6 kN
Deflection class Maximum deflection
A ( the most stringent )
2.5 mm
B 3.0 mm
C ( the least stringent )
4.0 mm